Call Us: 1300 093 795
Email Us: enquiry@elek.com.au

  • Login Cable Pro
Menu
  • Login Cable Pro
Electrotechnik
  • Software
    • Cable Pro Web (AU)
    • Cable Pro Web (UK)
    • Protection Coordination
    • SafeGrid Earthing
    • Cable High Voltage
    • Cable Pulling
    • Bare Conductor Ratings
    • Power Bundle
  • Resources
    • Article Categories
      • Low Voltage Design
      • Earthing Design
      • High Voltage Cable Design
      • Electrical Software
      • Arc Flash Studies
    • Tutorials
    • Free Calculators
      • Cable Sizing AS3008
      • Cable Sizing BS7671
      • Voltage Drop
      • Arc Flash
      • Earth Cable Sizing
      • Fault Loop Impedance
      • Earth Grid Resistance
      • Earth Grid Conductor Sizing
      • Earthing Rods Resistance
      • Lightning Protection Design
      • Relay Tripping Time
      • Equivalent Thermal Resistance
    • Courses
      • SafeGrid Earthing Software Course
    • Technical Publications
    • Training and Certification
  • Support
    • Support Overview
    • Help Portal
  • About
    • About Us
    • Contact Us
    • Careers
    • Reseller & Partner Program
  • Login
    • Cable Pro Web Login
    • Training Courses Login
    • Customer Licence Portal
  • TRY FOR FREE
  • SCHEDULE A DEMO
  • TRY FOR FREE
  • SCHEDULE A DEMO
  • TRY FOR FREE
Menu
  • Software
    • Cable Pro Web (AU)
    • Cable Pro Web (UK)
    • Protection Coordination
    • SafeGrid Earthing
    • Cable High Voltage
    • Cable Pulling
    • Bare Conductor Ratings
    • Power Bundle
  • Resources
    • Article Categories
      • Low Voltage Design
      • Earthing Design
      • High Voltage Cable Design
      • Electrical Software
      • Arc Flash Studies
    • Tutorials
    • Free Calculators
      • Cable Sizing AS3008
      • Cable Sizing BS7671
      • Voltage Drop
      • Arc Flash
      • Earth Cable Sizing
      • Fault Loop Impedance
      • Earth Grid Resistance
      • Earth Grid Conductor Sizing
      • Earthing Rods Resistance
      • Lightning Protection Design
      • Relay Tripping Time
      • Equivalent Thermal Resistance
    • Courses
      • SafeGrid Earthing Software Course
    • Technical Publications
    • Training and Certification
  • Support
    • Support Overview
    • Help Portal
  • About
    • About Us
    • Contact Us
    • Careers
    • Reseller & Partner Program
  • Login
    • Cable Pro Web Login
    • Training Courses Login
    • Customer Licence Portal
  • TRY FOR FREE
  • SCHEDULE A DEMO
  • TRY FOR FREE
  • SCHEDULE A DEMO
  • TRY FOR FREE

Lightning Protection Calculator

Home / Resources / Electrical Design Calculators / Lightning Protection Calculator

Lightning Protection Calculator

This calculator determines the area protected by lightning protection equipment using the Rolling Sphere Method. The results show either the maximum distance for the lightning masts to be placed apart or the furthest distance for the equipment to be placed from the masts.

This is a simple calculator which uses empirical equations to solve for six (6) independent shielding cases which can be used in combination.  For an automated and accurate approach you should use the Lightning Protection Module of SafeGrid Earthing Software.

1. Standalone Mast:

In this case, the equipment is being protected by one mast. The inputs are the height of the mast (H) and the height of the equipment to be protected (Y). The outputs are the maximum distance (Lmax) for the equipment to be placed in order to always be protected.

1.Standalone mast 350x210 - Lightning Protection Calculator

2. Two Lightning Masts:

In this case, the inputs are the heights of the masts (H & h), the height of equipment to be protected (Y) and the distance between the masts (L).

2. 2 masts 1 350x210 - Lightning Protection Calculator

The calculator outputs the maximum possible distance between the masts (Lmax) so that the height Y can be the maximum height for the equipment to be protected anywhere between the masts (Ymax). If the user does not specify the distance, the calculator takes Lmax as the distance between the masts.2. 2 masts 2 350x210 - Lightning Protection Calculator

However, if Y is greater than Ymax and lower than both masts, the calculator displays Lmax, Ymax, the maximum distance for the equipment to be protected from the higher mast (L1) and the maximum distance for the equipment to be protected from the lower mast (L­2).

2.2 masts top 1 350x210 - Lightning Protection Calculator2.2 masts top 2 350x210 - Lightning Protection Calculator

If Y is greater than the lower mast, Lmax  is not applicable, and a distance input field is mandatory. The calculator in this case outputs Ymax and L1.

Other outputs are:

LextH: the external protected area of the higher mast.

Lexth: the external protected area of the lower mast.

X: the minimum width of the protected area.

3. Mast and fence:

In this case, the user needs to input the heights of the mast and the fence (H & f), the height of equipment to be protected (Y) and the distance between the masts (L).3.Mast and fence 1 350x210 - Lightning Protection Calculator

The calculator outputs the maximum possible distance between the masts (Lmax) so that the height Y can be the maximum height for the equipment to be protected anywhere between the mast and the fence (Ymax). If the user does not specify the distance, the calculator takes Lmax as the distance between the mast and the fence.

3.Mast and fence 2 350x210 - Lightning Protection Calculator

If Y is greater than the fence, Lmax  would not be applicable, and a distance input field will be mandatory. The calculator in this case outputs Ymax and L.

4. Gantry Conductors:

The height of equipment (i.e. phase conductors) must not be higher than Ymax to be fully protected. The gantry posts are at the same height. The inputs are the gantry posts height (H) and the height of equipment to be protected (Y). If the distance between gantry posts (L) is specified, the calculator outputs Ymax and Lmax. If the distance between masts is not specified, the distance between the masts (Lmax) will be so that Y will be the required Ymax­.

4.gantry conductors 350x210 - Lightning Protection Calculator

 

5. 3-Masts & 4-Masts:

The aim of these cases is to find the diameter (L) of the circumscribing circle of the three or four masts within which the equipment will be protected. The masts are all of the same height. The inputs are the height of the masts and the equipment height. The outputs are the diameter of the circle(L), (Lext) the external protected area and (X) the minimum width of the protected area.

5.3 masts 350x210 - Lightning Protection Calculator5.3 masts top 350x210 - Lightning Protection Calculator

 

64 masts top 350x210 - Lightning Protection Calculator6.4 masts 350x210 - Lightning Protection Calculator

Related Resources:

Earth Grid Conductor Size Calculator - Lightning Protection Calculator

Earth Grid Conductor Size Calculator

This calculator determines the minimum earth grid conductor size based on the short-time temperature rise limit and is based on equation 37 (section 11.3.1) from IEEE Guide for Safety in AC Substation Grounding (IEEE Std. 80-2013).

Try It Now
Earthing Grid Resistance IEEE Std. 80 Calculator - Lightning Protection Calculator

Earthing Grid Resistance IEEE Std. 80 Calculator

This calculator produces the grid resistance within a substation based on several parameters such as total buried length of conductors, area occupied by ground grid and the depth of the grid.

Try It Now

Lightning Protection Software

SafeGrid 350x210 - Lightning Protection Calculator

Automatic lightning protection system design using the rolling sphere method.

Try For Free

As used by:

safegrid sidebar 1 - Lightning Protection Calculator

For information or to speak with our helpful advisors

GET IN TOUCH

GET IN TOUCH

Electrotechnik-Footer

Electrical Power Systems Design & Analysis Software

FOLLOW US

social-fb
social-yt
social-li

SOFTWARE

  • Cable Pro Web
  • Protection Coordination
  • SafeGrid Earthing
  • Cable High Voltage
  • Cable Pulling
  • Line Rate
  • Power Bundle
Menu
  • Cable Pro Web
  • Protection Coordination
  • SafeGrid Earthing
  • Cable High Voltage
  • Cable Pulling
  • Line Rate
  • Power Bundle

RESOURCES & SUPPORT

  • Software Tutorials
  • Technical Publications
  • Training and Certification
  • Customer Licence Portal
Menu
  • Software Tutorials
  • Technical Publications
  • Training and Certification
  • Customer Licence Portal

CONTACT US

Email:
enquiry@elek.com.au

Need Help?
Lodge a Support Ticket

Phone:
1300 093 795
International:
+61 (0)2 8231 6673

FREE TECHNICAL NEWS

© 2022 All Rights Reserved    Privacy Policy Quality Policy Terms of Use

Schedule a Demo for Cable High Voltage

Look No Further. Get Started Today

  • This field is for validation purposes and should be left unchanged.
Schedule a Demo for SafeGrid Earthing

Look No Further. Get Started Today

  • This field is for validation purposes and should be left unchanged.
SafeGrid Earthing Free Trial
  • Fill out your details below to begin your trial. Once your information has been submitted you'll be able to download the software.

  • This field is for validation purposes and should be left unchanged.
Cable High Voltage Free Trial
  • Fill out your details below to begin your trial. Once your information has been submitted you'll be able to download the software.

  • This field is for validation purposes and should be left unchanged.
SafeGrid Earthing 14 day Free Trial

Fill out your details below to begin your trial. Once your information has been submitted you’ll be able to download the software.

  • Fill out your details below to begin your trial. Once your information has been submitted you'll be able to download the software.

  • This field is for validation purposes and should be left unchanged.

CLOSE

Cable High Voltage 14 day Free Trial

Fill out your details below to begin your trial. Once your information has been submitted you’ll be able to download the software.

  • Fill out your details below to begin your trial. Once your information has been submitted you'll be able to download the software.

  • This field is for validation purposes and should be left unchanged.

CLOSE

  • We strive for 100% customer satisfaction. If we fell short, please tell us more so we can address your concerns.

  • This field is for validation purposes and should be left unchanged.

If you do not wish to address your concerns here and prefer to post a review, click here.