Call Us: 1300 093 795
Email Us: enquiry@elek.com.au

  • Login Cable Pro
Menu
  • Login Cable Pro
Electrotechnik
  • Software
    • Cable Pro Web (AU)
    • Cable Pro Web (UK)
    • Protection Coordination
    • SafeGrid Earthing
    • Cable High Voltage
    • Cable Pulling
    • Bare Conductor Ratings
    • Power Bundle
  • Resources
    • Article Categories
      • Low Voltage Design
      • Earthing Design
      • High Voltage Cable Design
      • Electrical Software
      • Arc Flash Studies
    • Tutorials
    • Free Calculators
      • Cable Sizing AS3008
      • Cable Sizing BS7671
      • Voltage Drop
      • Arc Flash
      • Earth Cable Sizing
      • Fault Loop Impedance
      • Earth Grid Resistance
      • Earth Grid Conductor Sizing
      • Earthing Rods Resistance
      • Lightning Protection Design
      • Relay Tripping Time
      • Equivalent Thermal Resistance
    • Courses
      • SafeGrid Earthing Software Course
    • Technical Publications
    • Training and Certification
  • Support
    • Support Overview
    • Help Portal
  • About
    • About Us
    • Contact Us
    • Services
    • Careers
    • Reseller & Partner Program
  • Login
    • Cable Pro Web Login
    • Training Courses Login
    • Customer Licence Portal
  • TRY FOR FREE
  • SCHEDULE A DEMO
  • TRY FOR FREE
  • SCHEDULE A DEMO
  • TRY FOR FREE
Menu
  • Software
    • Cable Pro Web (AU)
    • Cable Pro Web (UK)
    • Protection Coordination
    • SafeGrid Earthing
    • Cable High Voltage
    • Cable Pulling
    • Bare Conductor Ratings
    • Power Bundle
  • Resources
    • Article Categories
      • Low Voltage Design
      • Earthing Design
      • High Voltage Cable Design
      • Electrical Software
      • Arc Flash Studies
    • Tutorials
    • Free Calculators
      • Cable Sizing AS3008
      • Cable Sizing BS7671
      • Voltage Drop
      • Arc Flash
      • Earth Cable Sizing
      • Fault Loop Impedance
      • Earth Grid Resistance
      • Earth Grid Conductor Sizing
      • Earthing Rods Resistance
      • Lightning Protection Design
      • Relay Tripping Time
      • Equivalent Thermal Resistance
    • Courses
      • SafeGrid Earthing Software Course
    • Technical Publications
    • Training and Certification
  • Support
    • Support Overview
    • Help Portal
  • About
    • About Us
    • Contact Us
    • Services
    • Careers
    • Reseller & Partner Program
  • Login
    • Cable Pro Web Login
    • Training Courses Login
    • Customer Licence Portal
  • TRY FOR FREE
  • SCHEDULE A DEMO
  • TRY FOR FREE
  • SCHEDULE A DEMO
  • TRY FOR FREE

Home / Articles / Earthing Design

Soil Frequency Dependency During Lightning Strikes

Earthing system behaviour at high-frequencies
1653971060513 - Soil Frequency Dependency During Lightning Strikes

Soil electrical parameters at high frequencies

Soil electrical resistivity is one of the most important parameters to consider when designing safe earthing systems especially when analysing behaviour during lightning strikes.

Lightning currents can be represented by around 20,000 distinct frequency components ranging from DC up to several megahertz. Both soil electrical conductivity and permittivity are interrelated according to the Kramers-Kronig relation which goes back to Maxwell’s equations.

As frequency increases soil effective conductivity increases (resistivity decreases) while effective permittivity decreases, caused by soil ionisation at the high frequencies.

Calculating soil frequency dependency

There are several methods for calculating soil frequency dependency which are explained in CIGRE C4 Technical Brochure 781 [1] where the input to the functions is low frequency DC resistivity.  Note that the calculation methods have different frequency range limits for their applicability.

Figure 1 below shows the variation of soil electrical resistivity and relative permittivity (both very important factors for predicting earthing system performance) with increasing frequency based on seven (7) different calculation methods [1]. For example, based on the CIGRE calculation method relative (normalised) soil electrical resistivity is reduced by 34.4 % between 100 Hz and 1 MHz. 

 

Variation of soil electrical resistivity and relative permittivity with frequency
Figure 1 -Variation of soil electrical resistivity and relative permittivity with frequency

Here is an example calculation for a real-world horizontally-stratified soil resistivity model:

A 3-layer soil resistivity model for DC (or power frequency) = [10, 300, 1000] Ω.m

The same soil model at 1 MHz considering soil frequency dependence (CIGRE method was used) = [9.57, 196.7, 441.45] Ω.m

Soil frequency dependence has a favourable effect on earthing systems – grid resistance is reduced with increased frequency.

When to consider soil frequency dependency

Soil frequency dependency is obviously irrelevant at low frequencies and power frequencies under 100 Hz. This is a different consideration at higher frequencies.

The effect of frequency dependency on soil parameters is important to be considered especially when the soil resistivity values are high.

CIGRE C4 TB 781 [1] suggests for buried and transmission line earthing applications that frequency dependency can be ignored for soil resistivities less than 300 Ω.m, recommends it for soil resistivities between 300 and 700 Ω.m, and considers it mandatory for soils above 700 Ω.m.

Figure 2 below summarises the CIGRE recommendations pertaining to earthing system application.

Figure 2. CIGRE TB 781 recommendations concerning whether or not the frequency dependence of the soil parameters should be considered
Figure 2. CIGRE TB 781 recommendations concerning whether or not the frequency dependence of the soil parameters should be considered

If soil frequency dependency is ignored

During high-frequency faults such as lightning strikes, if constant soil electrical parameters are assumed and soil frequency dependency is ignored the voltage and current responses of an earthing system will be considerably overestimated.

Figure 3 below shows the high-frequency transient voltage (GPR) response for an earthing system with and without considering soil frequency dependency.

Figure 3. Earthing system transient (lightning current) response with or without considering soil frequency dependency
Figure 3. Earthing system transient (lightning current) response with or without considering soil frequency dependency

Figure 4 below demonstrates that if soil frequency dependency is ignored for high frequency currents then surface voltages for an earthing system will be completely different compared to if soil frequency dependency is included in the model.

Figure 4. Surface voltages for 30 m square grid in 700 Ohm. m soil for 1 Mhz injected current. Left plot has no soil frequency dependency considered while right plot has used the CIGRE method.
Figure 4. Surface voltages for 30 m square grid in 700 Ohm. m soil for 1 Mhz injected current. Left plot has no soil frequency dependency considered while right plot has used the CIGRE method.

Conclusions

It is important to understand that the behaviour of earthing systems at high frequencies compared with low frequencies is very different. Soil frequency dependency needs to be considered for earthing system modelling and calculations in order to predict performance which closely matches with actual behaviour.

References:

[1] CIGRE Technical Brochure 781 – Impact of soil-parameter frequency dependence on the response of grounding electrodes and on the lightning performance of electrical systems, 2019.

Related Articles:

elek article header ed fundamentals sm - Soil Frequency Dependency During Lightning Strikes

Fundamentals of Earthing Design

This tutorial introduces key concepts used in the design of substation earthing/grounding systems. Important terminology is discussed including Grid Potential Rise, touch and step voltages and current distribution.

Read It Now
elek article header ed benchmark sm - Soil Frequency Dependency During Lightning Strikes

Earthing Software Benchmark Study

The Annex H in IEEE Standard 80-2013 contains benchmark case results for comparing and evaluating software tools and methodologies used for the analysis of substation earthing.

Read It Now

SafeGrid Earthing Software

Easily design safe earthing systems in compliance with Standards.

Try For Free

Print this article:

Share on print
Print

SafeGrid Earthing Software

SafeGrid Earthing Software

Easily design safe earthing systems in compliance with Standards.

Try For Free

As used by:

For information or to speak with our helpful advisors

GET IN TOUCH

GET IN TOUCH

Electrotechnik-Footer

Electrical Power Systems Design & Analysis Software

FOLLOW US

social-fb
social-yt
social-li

SOFTWARE

  • Cable Pro Web
  • Protection Coordination
  • SafeGrid Earthing
  • Cable High Voltage
  • Cable Pulling
  • Line Rate
  • Power Bundle
Menu
  • Cable Pro Web
  • Protection Coordination
  • SafeGrid Earthing
  • Cable High Voltage
  • Cable Pulling
  • Line Rate
  • Power Bundle

RESOURCES & SUPPORT

  • Software Tutorials
  • Technical Publications
  • Training and Certification
  • Customer Licence Portal
Menu
  • Software Tutorials
  • Technical Publications
  • Training and Certification
  • Customer Licence Portal

CONTACT US

Email:
enquiry@elek.com.au

Need Help?
Lodge a Support Ticket

Phone:
1300 093 795
International:
+61 (0)2 8231 6673

FREE TECHNICAL NEWS

© 2022 All Rights Reserved    Privacy Policy Quality Policy Terms of Use

SafeGrid Earthing 14 day Free Trial

Fill out your details below to begin your trial. Once your information has been submitted you’ll be able to download the software.

  • Fill out your details below to begin your trial. Once your information has been submitted you'll be able to download the software.

  • This field is for validation purposes and should be left unchanged.

CLOSE

Schedule a Demo for Cable High Voltage

Look No Further. Get Started Today

  • This field is for validation purposes and should be left unchanged.
Schedule a Demo for SafeGrid Earthing

Look No Further. Get Started Today

  • This field is for validation purposes and should be left unchanged.
SafeGrid Earthing Free Trial
  • Fill out your details below to begin your trial. Once your information has been submitted you'll be able to download the software.

  • This field is for validation purposes and should be left unchanged.
Cable High Voltage Free Trial
  • Fill out your details below to begin your trial. Once your information has been submitted you'll be able to download the software.

  • This field is for validation purposes and should be left unchanged.
Cable High Voltage 14 day Free Trial

Fill out your details below to begin your trial. Once your information has been submitted you’ll be able to download the software.

  • Fill out your details below to begin your trial. Once your information has been submitted you'll be able to download the software.

  • This field is for validation purposes and should be left unchanged.

CLOSE

  • We strive for 100% customer satisfaction. If we fell short, please tell us more so we can address your concerns.

  • This field is for validation purposes and should be left unchanged.

If you do not wish to address your concerns here and prefer to post a review, click here.

Cable Pro (PC) Free Trial

Fill out your details below to begin your trial. Once your information has been submitted you’ll be able to download the software.

  • Fill out your details below to begin your trial. Once your information has been submitted you'll be able to download the software.

  • This field is for validation purposes and should be left unchanged.

CLOSE