How to model conductors surrounded by additional substance using SafeGrid

Model the effects of Bentonite, Marconite or equivalent enhancement materials surrounding buried earthing conductors.

Share on facebook
Facebook
Share on twitter
Twitter
Share on google
Google+
Share on linkedin
LinkedIn
Share on print
Print

Problem

To model the influence of an additional substance surrounding the conductors of a buried earthing system on grid resistance, touch and step voltages.

Solution

Treat the actual buried conductor and surrounding substance combined as a buried conductor of an equivalent (calculated) radius.
Figure 1 Earthing grid parameters with conductor surrounded by an additional substance.
Figure 2 Earthing grid parameters with conductor surrounded by an additional substance.

Approximate analytical equation

 

Where

Example

Model in SafeGrid under Design Settings

Reference

[1]  Kurtovic, M. and Vujevic, S. “Earthing grid parameters with conductor surrounded by an additional substance.”, IEEE Transactions, 2000