Low voltage cable derating factors -
Australian and New Zealand conditions
The current rating of a cable is affected by the presence of certain external influences. Under such conditions the current ratings given from the standard AS/NZS 3008.1 shall be corrected by the application of an appropriate factor or factors. Where more than one derating factor applies these shall be multipled to obtain an overall derating factor.
You can determine derating factors by hand from the Standards or using software.
Cable Pro Web software has a simple-to-use Wizard for derating factors. Try Now for Free.
Installation conditions that avoid derating
Derating factors may be avoided per Section 3.5.2.2 of AS/NZS 3008.1 including:
(a) Mineral insulated (MIMS) cables without serving unless other types of cables are installed in close proximity or within the same wire enclosure.
(b) Limited length of grouping where length does not exceed and whichever is shorter:
(i) 1 m for conductor sizes < 300 mm2 aluminium or < 150 mm2 for copper; or
(ii) 3 m for conductor sizes 300 mm2 or larger aluminium and 150 mm2 or larger for copper; or
(iii) half the length of the cable.
(c) Cables operating at less than 35 % of their rated current capacity.
Derating factor tables
The derating factor Tables below are from both AS/NZS 3008.1.1 (Australian conditions) and AS/NZS 3008.1.2 (New Zealand conditions). The Tables from both standards are the same except for TABLE 27(1) and 27(2) which differ.
Disclaimer: No responsibility is assumed for the accuracy of the Tables below. Further, there are additional notes to these tables which have not been included.
In Air





Buried - General



Buried - Direct



Buried - Enclosures



To purchase standards please visit: https://www.saiglobal.com
Related Articles:
Voltage Rise
Calculations
Voltage rise occurs in solar PV systems on the AC side between the power inverters and the network connection when power flows from the inverter back into the network.
Understanding Earth
Fault Loop Impedance
The purpose of this article is to provide a better understanding of Fault Loop Impedance, also referred to as Earth Fault Loop Impedance so that the requirements of …