Accurate voltage drop calculations

Using resistance and reactance, operating temperature and power factor

Accurately calculating voltage drop results in lower voltage drops which leads to smaller cable sizes and saves money.

You can calculate voltage drop by hand or using software.

Cable Pro Web software performs accurate voltage drop calculations. Try Now for Free.

To accurately calculate voltage drop in cables utilise:

  • Conductor resistance, Rc (in Ohms/m) values based on actual cable operating temperature (from the actual current loading percentage).
  • Conductor reactance, Xc (in Ohms/m) values. Xc = 0 for d.c. installations.
  • Load power factor (cosθ).
  • Accurate cable route length (L).
  • Actual maximum operating load current (I).

For single phase:

For three phase:

The values for Rc and Xc are provided in the Standards.

The conductor resistance is lower when you consider the actual operating temperature. Using resistance values at the actual cable operating temperature results in more accurate and less conservative (lower) voltage drop than if you were to consider the cable to be at its maximum operating temperature.

References

Standard AS/NZS 3008.1.1 Electrical Installations-Selection of cables

Related Articles:

Voltage Drop Limits

The voltage drop between the point of supply for the low voltage electrical installation and any point in that electrical installation must not exceed 5 % of the nominal voltage of the point of supply.

Voltage Rise Calculations

Voltage rise occurs in solar PV systems on the AC side between the power inverters and the network connection when power flows from the inverter back into the network.

Cable Pro Web

Cable sizing and maximum demand software in the cloud. No installation, use on any device.

Print this article:

Share on print
Print
Cable Pro Web

Cable sizing and maximum demand software in the cloud.

As used by: