Overview

The following tutorial is designed to help users of SafeGrid Earthing Software to learn about and practice the application of powerful operating tools and principles.

Mobile phone repeater station earthing arrangement

The mobile phone repeater station earthing consists of interconnected grid conductors covering the lease area of 9 m by 14.5 m of conductors buried at a depth of 0.5 m.  The grid is buried at separation distances of 0.5 m and 1 m from the perimeter fence and the shelter building respectively.

There are three 1 m2 buried plates underneath the concrete pad footing for each leg of the antenna structure.

Rods of 12 m lengths are added as required to reduce the overall earthing resistance.

 

Figure 1. Sketch of mobile phone repeater station earthing system.

Purpose of the earthing system

The purpose of the earthing system is to provide a low impedance path to the earth from personnel and equipment protection during lightning strikes.
The customer has specified that the total earth grid impedance must not exceed 5 Ω.

 

Modelling the earth grid in SafeGrid

The earthing grid was drawn using CAD software and imported into SafeGrid as a DXF file.  Figure 2 shows the CAD model for earthing arrangement. 
The model includes the metal plates which were modelled as tightly meshed straight line connected segments.

 

Figure 2. Model of earth grid drawn in CAD and saved as DXF file for importing into SafeGrid.
Figure 3. DXF CAD file imported into SafeGrid.
Figure 3. DXF CAD file imported into SafeGrid.

 

Soil resistivity modelling

Soil resistivity measurements were taken in the field using the Wenner Array Method at electrode spacing’s of between 1 m and 8 m due to space limitations. 
Two sets of measurements were taken in different directions.  Note it is good practice to take at least 5 measurements per set.

Figure 4 Wenner field resistivity measurements.
The calculated 2-layer soil model using E-W measurements was as follows (Figure 4):
Top layer resistivity = 6390 Ω-m
Depth of top layer = 3.13 m
Bottom layer resistivity = 139.3 Ω-m
Goodness of fit = 0.928 (very good)
 

SafeGrid Results – calculated grid resistance

Grid resistance was calculated for the various cases as follows:

 

Figure 5 Grid resistance was calculated for the various cases.
 

Plot of grid resistance versus no. of rods

Adding rods is very effective at reducing the grid resistance.  This is because the rods are penetrating the relatively low resistivity bottom soil layer.
 

 

Figure 6. Plot of grid resistance versus no. of rods.

 

Conclusion – No. of rods required

In conclusion adding 4 rods to the grid at the corners is enough to reduce the grid resistance to below 5 Ω.
 